RANGE OF PRODUCTS
METERING UNITS approved ERDA
IGNITION TRANSFORMER
BATTERY CHARGER
PHANTOM LOAD TEST
AC HIGH VOLTAGE
DC HIGH VOLTAGE
CURRENT INJECTION SET
OIL TEST SET
METER TEST BENCH
RELAY TEST SET

Test report approved by ERDA


CT / PT METERING UNITS
ITEM CT/PT METERING UNITS 33 KV, 22 KV, 11 KV
APPLICATION POWER STATIONS & MAJOR POWER CONSUMERS WHO METER ENERGY CONSUMPTION MAXIMUM DEMAND ETC.
SPECIFICATION INPUT : 33 KV, 11KV, 3PH 50 HZ A.C
OUTPUT IN VOLTAGE : 110V-3 PH 40 HZ A.C
CURRENT : 5 AMP.
VA FOR VOLTAGE : PT - 100
VA FOR CURRENT : CT - 15
CLASS OF ACCURACY : 1% / 0.5% ERROR
SYSTEM VOLTAGE : 12KV (11KV), 24KV (22KV) 36KV (33KV)
INSULATION LEVEL : 28KV, 50KV, 75KV
IMPULSE VOLTAGE :
IMPULSE CURRENT :
COOLING : AN ON
BENIFITS COMPACT DESIGN, CONFIRMING TO RELEVANT STANDARD, LONG LIFE.
Test report approved by ERDA


CT / PT METERING UNITS
ITEM CT/PT METERING UNITS 33 KV, 22 KV, 11 KV
APPLICATION POWER STATIONS & MAJOR POWER CONSUMERS WHO METER ENERGY CONSUMPTION MAXIMUM DEMAND ETC.
SPECIFICATION INPUT : 33 KV, 11KV, 3PH 50 HZ A.C
OUTPUT IN VOLTAGE : 110V-3 PH 40 HZ A.C
CURRENT : 5 AMP.
VA FOR VOLTAGE : PT - 100
VA FOR CURRENT : CT - 15
CLASS OF ACCURACY : 1% / 0.5% ERROR
SYSTEM VOLTAGE : 12KV (11KV), 24KV (22KV) 36KV (33KV)
INSULATION LEVEL : 28KV, 50KV, 75KV
IMPULSE VOLTAGE :
IMPULSE CURRENT :
COOLING : AN ON
BENIFITS COMPACT DESIGN, CONFIRMING TO RELEVANT STANDARD, LONG LIFE.


IGNITION TRANSFORMER
ITEM IGNITION TRANSFORMER OF 5 KV, 7.5 KV, 10 KV, 12 KV, 14.5 KV.
APPLICATION FURNACES IN WHICH SPARK IGNITION IS USED.
SPECIFICATION INPUT : 230 V, 1 PH 50 HZ A.C
OUTPUT : 5 KV, 7.5 KV, 10 K.V, 12 K.V, 14.5 KV.
CURRENT : 20MA, 35MA
DUTY : CONTINUOUS / INTERMITTENT
TYPE : EPOXY RESIN / DAMPER MOLDED
BENIFITS COMPACT DESIGN, MAINTENANCE FREE, LONG LIFE PANEL MOUNTABLE.


BATTERY CHARGER (FLOAT & BOOST)
ITEM BATTERY CHARGES OF ALL TYPES OF SECONDARY CELLS OF ALL CAPACITY.
APPLICATION BACKUP POWER SUPPLY FOR POWER STATIONS, CONTINUOUS PRODUCTION UNITS, RAILWAYS, HOSPITALS, HOTELS, COMMUNICATION SYSTEMS, COMPUTER INSTALLATIONS ETC.
SPECIFICATION INPUT : 230 / 440 V - 1PH / 3 PH, 50 HZ A.C.
OUTPUT : D.C UP TO 230 / 440 V ETC.
O/P CAPACITY : AS PER REQUIREMENT (OPTIONAL)
RECTIFICATION : DIODE / SCR, FULL WAVE / HALF WAVE CONTROLLED DIRECT.
RIPPLE / FILTERING : RIPPLE AS PER REQUIREMENT.
FILTERING ADOPTED.
EFFICIENCY : MORE THAN 80%
POWER FACTOR : 08
MODE OF OPERATION : INITIAL, BOOST, FLOAT, TRICKLE.
CONTROL : MANUAL / AUTOMATIC
DUTY : CONTINUOUS
OVERLOAD : 50 % FOR 1 HOUR
COOLING : A.N
INSTALLATION : INDOOR / OUTDOOR, FIXED / PORTABLE (OPTIONAL)
BENIFITS SINGLE CUBICLE CONSTRUCTIONS, VOLTAGE AND CURRENT SELECTION, AUTOMATIC VOLTAGE AND CURRENT REGULATOR, DIGITAL / ANALOG METERING (OPTIONAL), OPERATION MODE FACILITY, PROTECTION FOR TRANSFORMERS & RECTIFIER UNITS, LONG LIFE & LESS MAINTENANCE, RISK FREE OPERATION



INSTRUMENT TRANSFORMER
ITEM INSTRUMENT TRANSFORMER UP TO 22 KV, CURRENT TRANSFORMERS AND POTENTIAL TRANSFORMERS.
APPLICATION FOR METERING OF HIGH VOLTAGE & CURRENT OF DIFFERENT POWER SYSTEM & PANEL BOARDS. FOR PROTECTION OF THE ABOVE TO FEED THEIR CONTROL SYSTEMS AND SWITCH GEARS.
SPECIFICATION INPUT : HIGH VOLTAGE & HIGHER CURRENT OF POWER SYSTEMS
OUTPUT : PT - 110 V OR AS PER REQUIREMENTS.
COOLING: AN / ANON
CONSTRUCTION : OIL IMMERSED / RESIN CAST / OPEN TYPE.
BENIFITS DESIGN AS PER REQUIREMENTS. CONFIRMING TO STANDARDS, INDOOR / OUTDOOR DESIGN, HIGHER PRECISION LEVEL.


A.C HIGH VOLTAGE TEST SET
ITEM A.C HIGH VOLTAGE TEST SETS (LOW POWER) UP TO 100 KV
APPLICATION TESTING OF COILS, CABLES, TRANSFORMERS ETC.
SPECIFICATION INPUT : 230 / 440 V, 1 PH 50HZ 5% +/-
OUTPUT : UP TO 100 KV
CURRENT SETTING: UP TO 500MA
AMBIENT TEMP : 50 DEGREES C
HUMIDITY : 100% MAXIMUM
ATMOSPHERE : DUSTY / HYGROSCOPIC
INSTALLATION : INDOOR PORTABLE
ALTITUDE : 1000M ABOVE M.S.L
TEMP. RISE : 55 DEGREES C
TEMP. LIMIT OF
INSULATION : 115 DEGREES C
DUTY : HOUR ON / HOUR OFF
OVERLOAD : 10%
METHOD OF
COLLING : ONAN
PRIMARY CURRENT
OVERLOAD LIMIT : 2.5 TIMES FULL LOAD
OPERATION : MANUAL / MOTORIZED (OPTIONAL)
CURRENT RELATION : OPTIONAL
BENIFITS SINGLE TWO PART CONSTRUCTION, MEMORY SET UP FOR O/P VOLTAGE, OVERLOAD / TRIPPING CURRENT SETTING, BROUGHT OUT H.T TERMINAL BUSHING, MULTIPLE OPERATOR SAFEGUARD, DIGITAL / ANALOGUE METERING (OPTIONAL), EFFECTIVE SURGE SUPPRESSOR, TIME SETTING ARRANGEMENT.

       

D.C HIGH TENSION POWER SUPPLY
ITEM D.C HIGH TENSION POWER SUPPLY UP TO 100 KV, WITH CURRENT CAPACITIES UP TO 350mA.
APPLICATION TESTING OF INSULATION LEVEL & ISOLATION OF CONDUCTORS IN WINDINGS & CABLES ETC.
SPECIFICATION INPUT : 230 / 440 V, 1 PH 50HZ 5% +/-
OUTPUT : UP TO 100 KV D.C
CAPACITY : UP TO 350MA
AMBIENT TEMP : 50 DEGREES C
HUMIDITY : 100% MAXIMUM
ATMOSPHERE : DUSTY / HYGROSCOPIC
INSTALLATION : INDOOR PORTABLE
ALTITUDE : 1000MTR OVER MSL
TEMP. RISE : 55 DEGREES C
TEMP. LIMIT OF
INSULATION : 115 DEGREES C
DUTY : HOUR ON / HOUR OFF
OVERLOAD : 10%
METHOD OF
COLLING : ONAN / AN
PRIMARY OVER
CURRENT LIMIT : 2.5 TIMES OVERLOAD
OPERATION : MANUAL / AUTOMATIC
CURRENT SELECTION : OPTIONAL
BENIFITS COMPACT DESIGN, DIRECT OUTPUT METERING, OVERLOAD / TRIPPING CURRENT PROTECTION AND SETTINGS, BROUGHT OUT H.T TERMINAL, MULTIPLE OPERATOR SAFEGUARDS, ALARM / INDICATION DIGITAL / ANALOGUE METERING (OPTIONAL), + VE / - VE EARTHING ARRANGEMENT.



CURRENT INJECTION SET
ITEM CURRENT INJECTION SET
APPLICATION TEST IN OF RELAYS AND METER
SPECIFICATION INPUT : 230 / 440 V, 1 PH 50 MZ AC. OUTPUT : 1.7 V. CURRENT : 4000 AMPS. COOLING : AIR NATURAL OPERATION : MANUAL INSTALLATION : INDOOR AS WELL AS OUTDOOR (PORTABLE) ATMOSPHERE : DUSTY / HYGROSCOPE TEMP. RISE : 115 C
BENIFITS COMPACT DESIGN, LONG LIFE, TROUBLE FREE IF USED WITHIN ELECTRICAL, MECHANICAL AND ENVIRONMENTAL LIMITATIONS


OIL TEST SET
ITEM TRANSFORMER OIL TEST SETS 50, 60, 100 KV.
APPLICATION FOR TESTING THE DIELECTRIC STRENGTH OF TRANSFORMER INSULATION OIL.
SPECIFICATION INPUT : 230 V 1 PH 50 HZ A.C 5% +/- OUTPUT : 0 - 50 / 60/100 KV CURRENT : 20MA SETTING HUMIDITY : 100% MAXIMUM ATMOSPHERE : DUSTY / HYGROSCOPIC INSTALLATION : INDOOR / PORTABLE ALTITUDE : 1000M ABOVE M.S.L TEMP. RISE : 55 DEGREES C DUTY : INTERMITTENT OVERLOAD : 10% METHOD OF COOING : A.N OPERATION : MANUAL / MOTORIZED CONTROL : FAST ACTING SEMI CONDUCTOR CONTROL.
BENIFITS COMPACT DESIGN, VISUAL ALARM TEST ASSESSMENT, BREAK DOWN VOLTAGE MEMORY SET UP, DIGITAL / ANALOGUE METERING (OPTIONAL), OPERATOR SAFEGUARD ARRANGEMENT.


METER TEST BENCH
ITEM METER TEST BENCH
APPLICATION TESTING AND CALIBRATION OF 3 PHASE 3 WIRE. ACTIVE & REACTIVE TYPE ENERGY METERS.
SPECIFICATION INPUT : 415 V, 3 PHASE, 50 HZ AC.
INPUT TOLERANCE : +/- 15%
OUTPUT : 0-63.5 X 3 / 240 X 3 V.
CAPACITY : 200 VA / PHASE
CURRENT : 0-1 / 2.5 / 5 / 10 / 25 / 50 / 100 A
CAPACITY : 200 VA / PHASE
PHASE SHIFT : 0-360 IN STEPS OF 30 DEGREE COARSE CONTROL 15 LAG - 15 LEAD STEP LESS FINE CONTROL.
INSTALLATION : INDOOR USE ONLY.
METHOD OF
COOLING : AIR NATURAL
OPERATION : MANUAL
AMBIENT TEMP. : 45 C.


RELAY TEST SET
ITEM RELAY TEST SET TO TEST
APPLICATION TO TEST EQUIPMENT WORKING ON A.C. VOLTAGE OR CURRENT RELAYS, CURRENT TRANSFORMER.
SPECIFICATION INPUT : 230 V, 1 PHASE 50 HZ A.C.
OUTPUT 0/75/300 V.
CAPACITY : 100 VA, 100AMPS.
INSTALLATION : INDOOR ONLY
METHOD OF
COOLING : AIR NATURAL
PRIMARY CURRENT : UP TO 1000AMPS.
DUTY : CONTINUOUS
CURRENT RELATION : OPTIONAL
EFFICIENCY : MORE THAN 80%
TEMP. RISE : 115C
OVERLOAD : 10%
BENIFITS SINGLE / TWO PART CONSTRUCTION CURRENT REGULATOR, RISK-FREE OPERATION, PROTECTION FOR TRANSFORMER AND METERS. DESIGNED AND DEVELOPED AS REQUIRED SPECIFICATIONS.
  Back  Next